Fire Pump Electric Motor Calculator Icon

Fire Pump Electric Motor Calculator App

Summary: Almost all three-phase electric fire pump motors are NEMA B, squirrel-cage type. This calculator uses the associated standard NEMA B NEC tables to look up the anticipated amperage and minimum conductor sizes.


INPUTS
Phases
Volts
Rated Horsepower
Anticipated Motor Currents
Locked-Rotor Current
Full Load Current
*Source:
ATL / Soft-Start (3-wire) Conductor Sizes
125% FLC (NEC 695.7(B))
Min Conductor Size
Min Conductor Size

* Must also confirm voltage drop per NEC 695.8: no more than 15 percent below normal at the controller line terminals during motor starting, and no more than 5 percent below the motor voltage rating at the contactor load terminals at 115 percent of FLC.

Wye-Delta (6-wire) Conductor Sizes
72% FLC (NEC 430.22(C))
Min Conductor Size
Min Conductor Size

* Must also confirm voltage drop per NEC 695.8: no more than 15 percent below normal at the controller line terminals during motor starting, and no more than 5 percent below the motor voltage rating at the contactor load terminals at 115 percent of FLC.

  • Voltage is the motor nameplate voltage, and the matching column of the NEC tables is used: 200 V, 230 V or 460 V. A 200 V nameplate is a different rating from 208 V, which has its own column in the NEC tables and is not offered here.
  • NEC 430.22(C), wye-start, delta-run motor: conductors between the controller and the motor are sized at 72 percent of the motor full-load current. Conductors on the line side of the controller are sized at 125 percent of FLC (see the ATL card).
  • Conductor sizes per NEC-2026 Table 310.16, 75°C column (NEC-2023: Table 310.15(B)(16); NEC-2020: Table 310.16). Types: RHW, THHW, THW, THWN, XHHW, XHWN, USE (and ZW for copper).
  • Code editions: all NEC references on this page are to NFPA 70 (NEC), 2026 edition: Table 310.16 (conductor ampacity), Tables 430.248 and 430.250 (full-load current), Tables 430.251(A) and 430.251(B) (locked-rotor current), 430.22(C) (wye-start, delta-run conductors), and 695.7(B) and 695.8 (fire pump conductor size and voltage drop). The only table numbered differently in the 2023 and 2020 editions is the conductor ampacity table, noted above.

Disclaimer: This calculator is for informational purposes only. It is not a substitute for the NEC or any other applicable codes, standards, or regulations. Always consult the NEC and local codes for final determinations.